CVS100F TM40D 3P3D – LV510333 Schneider Electric

Rp2.007.807

Moulded Case Circuit Breaker (MCCB) – Schneider Electric (EasyPact CVS) – CVS100F TMD 40A 3P3d – 3 poles (3P3d) – Rated current 40A – Short circuit breaking capacity (Icu) (380-415Vac) 36kA – Thermal-Magnetic (adjustable) trip unit (TMD) – Lug terminals

Stok 19

SKU: LV510333 Kategori: ,

Deskripsi

Range name EasyPact CVS
Main function Moulded Case Circuit Breaker (MCCB)
Sub-range name CVS100F
Rated Voltage (AC) – Phase-to-phase 440 V
Rated impulse voltage (Uimp) 8 kV
Rated insulation voltage (Ui) 690 V
Rated current 40 A
Frame current rating 100 AF
Trip current rating 40 AT
Ultimate short circuit current breaking capacity (Icu) (220-240Vac) 70 kA
(380-415Vac) 36 kA
(440Vac) 36 kA
Service short circuit current breaking capacity (Ics) (220-240Vac) 70 kA
(380-415Vac) 36 kA
(440Vac) 18 kA
Service short circuit current breaking capacity as a percentage of Icu (Ics%)(380-415Vac) 100 %
Poles 3 Pole(s)
Protected poles 3 Pole(s)
Utilisation category A
Compliant with standard(s) IEC60947-2
IEC60664-1
Electrical durability (with load) (415Vac; In/2) 30000 operations
(415Vac; In) 12000 operations
Mechanical durability (at no load) 30000 operations
Degree of pollution 3
Trip unit type TMD
Thermal-Magnetic (adjustable)
Protection function Thermal protection (Overload)
Magnetic protection (Short-circuit)
Protection settings (Over-current) adjustable from 0.7 – 1.0 x In
(Short-circuit) fixed at 500A
Type of terminals Lug
Functions Moulded Case Circuit Breaker (MCCB)
Primary brand Schneider Electric
Secondary brand Merlin Gerin
Class value
WhatsApp Kami
Select more than one item for comparison.