4P4D MICROLOGIC 2.3 630A NSX630F – LV432877 Schneider Electric

Moulded Case Circuit Breaker (MCCB) – Schneider Electric (Compact NSX) – NSX630F Micrologic 2.3 (LI) 630A 4P4d – 4 poles (4P4d) – Rated current 630A – Short circuit breaking capacity (Icu) (380-415Vac) 36kA – Electronic trip unit (Micrologic 2.3 (LI)) – Lug terminals

SKU: LV432877 Kategori: ,

Deskripsi

Range name Compact NSX
Main function Moulded Case Circuit Breaker (MCCB)
Sub-range name NSX630F
Rated Voltage (AC) – Phase-to-phase 690 V
Rated impulse voltage (Uimp) 8 kV
Rated insulation voltage (Ui) 800 V
Rated current 630 A
Frame current rating 630 AF
Trip current rating 630 AT
Ultimate short circuit current breaking capacity (Icu) (220-240Vac) 40 kA
(380-415Vac) 36 kA
(440Vac) 30 kA
(500Vac) 25 kA
(525Vac) 20 kA
(660-690Vac) 10 kA
Service short circuit current breaking capacity (Ics) (220-240Vac) 40 kA
(380-415Vac) 36 kA
(440Vac) 30 kA
(500Vac) 25 kA
(525Vac) 100 kA
(660-690Vac) 10 kA
Service short circuit current breaking capacity as a percentage of Icu (Ics%)(380-415Vac) 100 %
Poles 4 Pole(s)
Protected poles 4 Pole(s)
Utilisation category A
Compliant with standard(s) IEC60947-2
NEMA AB1
Electrical durability (with load) (440Vac; In/2) 8000 operations
(440Vac; In) 4000 operations
Mechanical durability (at no load) 15000 operations
Degree of pollution 3
Trip unit type Micrologic 2.3 (LI)
Electronic
Protection function L (Long-time protection)
S0 (Short-time protection with fixed time delay)
I (Instantaneous protection)
Protection settings L (Long-time protection) adjustable from 0.4 to 1 x In
S0 (Short-time protection with fixed time delay) adjustable from 1.5 to 10 x Ir
I (Instantaneous protection) fixed at 6900A
Type of terminals Lug
Functions Moulded Case Circuit Breaker (MCCB)
Primary brand Schneider Electric
Secondary brand Merlin Gerin
WhatsApp Kami
Select more than one item for comparison.