4P4D MICROLOGIC 2.3 400A NSX400H – LV432696 Schneider Electric

Moulded Case Circuit Breaker (MCCB) – Schneider Electric (Compact NSX) – NSX400H Micrologic 2.3 (LI) 400A 4P4d – 4 poles (4P4d) – Rated current 400A – Short circuit breaking capacity (Icu) (380-415Vac) 70kA – Electronic trip unit (Micrologic 2.3 (LI)) – Lug terminals

SKU: LV432696 Kategori: ,

Deskripsi

Range name Compact NSX
Main function Moulded Case Circuit Breaker (MCCB)
Sub-range name NSX400H
Rated Voltage (AC) – Phase-to-phase 690 V
Rated impulse voltage (Uimp) 8 kV
Rated insulation voltage (Ui) 800 V
Rated current 400 A
Frame current rating 400 AF
Trip current rating 400 AT
Ultimate short circuit current breaking capacity (Icu) (220-240Vac) 100 kA
(380-415Vac) 70 kA
(440Vac) 65 kA
(500Vac) 50 kA
(525Vac) 35 kA
(660-690Vac) 20 kA
Service short circuit current breaking capacity (Ics) (220-240Vac) 100 kA
(380-415Vac) 70 kA
(440Vac) 65 kA
(500Vac) 50 kA
(525Vac) 11 kA
(660-690Vac) 10 kA
Service short circuit current breaking capacity as a percentage of Icu (Ics%)(380-415Vac) 100 %
Poles 4 Pole(s)
Protected poles 4 Pole(s)
Utilisation category A
Compliant with standard(s) IEC60947-2
NEMA AB1
Electrical durability (with load) (440Vac; In/2) 12000 operations
(440Vac; In) 6000 operations
Mechanical durability (at no load) 15000 operations
Degree of pollution 3
Trip unit type Micrologic 2.3 (LI)
Electronic
Protection function L (Long-time protection)
S0 (Short-time protection with fixed time delay)
I (Instantaneous protection)
Protection settings L (Long-time protection) adjustable from 0.4 to 1 x In
S0 (Short-time protection with fixed time delay) adjustable from 1.5 to 10 x Ir
I (Instantaneous protection) fixed at 4800A
Type of terminal sLug
Functions Moulded Case Circuit Breaker (MCCB)
Secondary brand Merlin Gerin
WhatsApp Kami
Select more than one item for comparison.