3P3D TM160D NSX160N – LV430840 Schneider Electric

Moulded Case Circuit Breaker (MCCB) – Schneider Electric (Compact NSX) – NSX160N TMD 160A 3P3d – 3 poles (3P3d) – Rated current 160A – Short circuit breaking capacity (Icu) (380-415Vac) 50kA – Thermal-Magnetic (adjustable) trip unit (TMD) – Lug terminals

SKU: LV430840 Kategori: ,

Deskripsi

Range name Compact NSX
Main function Moulded Case Circuit Breaker (MCCB)
Sub-range name NSX160N
Rated Voltage (AC) – Phase-to-phase 690 V
Rated impulse voltage (Uimp) 8 kV
Rated insulation voltage (Ui) 800 V
Rated current 160 A
Frame current rating 160 AF
Trip current rating 160 AT
Ultimate short circuit current breaking capacity (Icu) (220-240Vac) 90 kA
(380-415Vac) 50 kA
(440Vac) 50 kA
(500Vac) 36 kA
(525Vac) 35 kA
(660-690Vac) 10 kA
Service short circuit current breaking capacity (Ics) (220-240Vac) 90 kA
(380-415Vac) 50 kA
(440Vac) 50 kA
(500Vac) 36 kA
(525Vac) 35 kA
(660-690Vac) 10 kA
Service short circuit current breaking capacity as a percentage of Icu (Ics%)100 %
Poles 3 Pole(s)
Protected poles 3 Pole(s)
Utilisation category A
Compliant with standard(s) IEC60947-2
NEMA AB1
Electrical durability (with load) (440Vac; In/2) 40000 operations
(440Vac; In) 20000 operations
Mechanical durability (at no load) 40000 operations
Degree of pollution 3
Trip unit type TMD
Thermal-Magnetic (adjustable)
Protection function Thermal protection (Overload)
Magnetic protection (Short-circuit)
Protection settings (Over-current) adjustable from 0.7 – 1.0 x In
(Short-circuit pickup current) fixed at 1250A
Type of terminal sLug
Functions Moulded Case Circuit Breaker (MCCB)
Primary brand Schneider Electric
Secondary brand Merlin Gerin
WhatsApp Kami