4P3D TM160D NSX160F – LV430640 Schneider Electric

Moulded Case Circuit Breaker (MCCB) – Schneider Electric (Compact NSX) – NSX160F TMD 160A 4P3d – 4 poles (4P3d) – Rated current 160A – Short circuit breaking capacity (Icu) (380-415Vac) 36kA – Thermal-Magnetic (adjustable) trip unit (TMD) – Lug terminals

SKU: LV430640 Kategori: ,

Deskripsi

Range name Compact NSX
Main function Moulded Case Circuit Breaker (MCCB)
Sub-range name NSX160F
Rated Voltage (AC) – Phase-to-phase 690 V
Rated impulse voltage (Uimp) 8 kV
Rated insulation voltage (Ui) 800 V
Rated current 160 A
Frame current rating 160 AF
Trip current rating 160 AT
Ultimate short circuit current breaking capacity (Icu) (220-240Vac) 85 kA
(380-415Vac) 36 kA
(440Vac) 35 kA
(500Vac) 30 kA
(525Vac) 22 kA
(660-690Vac) 8 kA
Service short circuit current breaking capacity (Ics) (220-240Vac) 85 kA
(380-415Vac) 36 kA
(440Vac) 35 kA
(500Vac) 30 kA
(525Vac) 22 kA
(660-690Vac) 8 kA
Service short circuit current breaking capacity as a percentage of Icu (Ics%)100 %
Poles 4 Pole(s)
Protected poles 3 Pole(s)
Utilisation category A
Compliant with standard(s) IEC60947-2
NEMA AB1
Electrical durability (with load) (440Vac; In/2) 40000 operations
(440Vac; In) 20000 operations
Mechanical durability (at no load) 40000 operations

Degree of pollution3
Trip unit typeTMD
Thermal-Magnetic (adjustable)
Protection functionThermal protection (Overload)
Magnetic protection (Short-circuit)
Protection settings(Over-current) adjustable from 0.7 – 1.0 x In
(Short-circuit pickup current) fixed at 1250A
(Neutral protection) none
Type of terminalsLug
FunctionsMoulded Case Circuit Breaker (MCCB)
Primary brandSchneider Electric
Secondary brandMerlin Gerin

WhatsApp Kami
Select more than one item for comparison.